| Specifications |
 |
12VDC operation (0.6A @ 12V, 0.3A @ 24V current consumption with all relays energized). |
 |
Power Supply Input Options:
1. One(1) Common power input (board and lock power).
2. Two(2) isolated power inputs (one[1] for board power,
one[1] for lock power). |
 |
Four(4)(HPACM4) access control system
trigger inputs (input allows any combination or normally
open [NO] inputs or open collector sink inputs). |
 |
Four(4)(HPACM4) independently controlled
outputs. |
 |
Output Options:
1. Two(2)(HPACM4) fail-safe and/or
fail-secure power outputs.
2. Two(2)(HPACM4) dry Form “C” 5A
rated relay outputs.
3. Any combination of the above. |
 |
Four(4)(HPACM4) or eight(8)(HPACM8) auxiliary power
outputs (unswitched). |
 |
PTC protected outputs are rated at 2.5A, power limited
class 2.
NOTE: Output current is determined by the power supply, not to
exceed 10A total. |
 |
Red LEDs indicate outputs are triggered (relays energized). |
 |
Fire Alarm Disconnect (latching or non-latching). |
 |
Fire Alarm Disconnect Input Options:
1. Normally open (NO) or normally closed (NC) dry contact
input.
2. Polarity reversal from FACP signals circuit. |
 |
Fire Alarm Disconnect Output Options:
1. Four(4)(HPACM4) outputs affected.
2. Two(2)(HPACM4) outputs affected,
two(2)(HPACM4) unaffected (50/50
mode). |
 |
FACP output relay (Form “C” contact rated @ 1A, 28VDC
not evaluated by UL). |
 |
Green LED indicates when FACP disconnect is triggered. |
 |
Removable terminal blocks facilitate ease of installation. |
 |
Board Dimensions:
– HPACM4: 6”L x 4.5”W x 1.25”H (cm: 15L x 11.3W x 3.2H) |
 |
UL Listed for Access Control Systems: UL294 |
 |
UL Listed for Fire Alarm Systems: UL1481 |
 |
UL Listed for Burglar Alarm Systems: UL603
NOTE: This unit has not been evaluated for elevator equipment
and is not authorized for bell output in Mercantile applications. |
| |
|
| Power Supply Specifications |
 |
Input Voltage: 120VAC, 60Hz, 2.5A max. |
 |
Output Voltage: 12VDC or 24VDC (jumper selectable). |
 |
4.0A continuous output max., 3.5A plus battery charger. |
 |
Fail safe dry contact output on AC failure (within one minute). |
 |
Built-in charger for sealed lead acid or gel cell type batteries. |
 |
Instantaneous transfer to stand-by battery on AC failure. |
 |
Battery presence detection (within one minute). |
 |
Battery low disconnect at 9.90VDC or 19.9VDC. |
 |
High voltage disconnect at 15VDC or 30 VDC and battery low. |
 |
Fail safe dry contact output for battery trouble (fail safe). |
 |
Battery polarity reversal protection. |
 |
Thermal overload and short circuit protection. |
 |
Yellow LED (L3) indication for battery disconnected. |
 |
DC output PTC activated indicated by red LED (L2). |
 |
DC output failure indicated by red LED (L4). |
 |
AC presence indicated by green LED (L1). |
 |
DC output indicated by red LED (L5). |
 |
Battery leads included. |
 |
Enclosure Dimensions: 13”H x 13.5”W x 3.25”D
NOTE: Enclosure accommodates up to two(2) 12AH batteries. |