| Specifications - Power Supply Board |
 |
Input voltage: 120VAC 60Hz; Current: 2.50A max. |
 |
Output Voltage: 12VDC or 24VDC, jumper selectable; Current: 4.0A continuous output maximum, 3.5A plus battery charger (not supervised). |
 |
Fail safe dry contact output on AC Failure (within one minute). |
 |
Built-in charger for sealed lead acid or gel cell type batteries. |
 |
Instantaneous transfer to stand-by battery on AC failure. |
 |
Battery presence detection (within 1 minute) |
 |
Battery low disconnect at 9.90VDC or 19.90VDC. |
 |
High voltage disconnect at 15VDC or 30VDC. |
 |
Yellow LED (L3) indication for battery disconnected and battery low. |
 |
Fail safe dry contact output for Battery trouble (Fail Safe). |
 |
Battery polarity reversal protection. |
 |
Thermal overload and short circuit protection. |
 |
DC output PTC activated indication by Red LED (L2). |
 |
DC output failure indication by Red LED ( L4 ). |
 |
AC presence indication by Green LED ( L1 ). |
 |
DC output indication by Red LED ( L5 ). |
 |
Battery Leads included. |
 |
Power Board Dimensions: 6.2”L x 4.7”W x 2.5”H. |
 |
Enclosure Dimension: 17”L x 13.5”W x 4.75”H. Accommodates two 12 Volt 12AH batteries. When using larger batteries, a UL approved enclosure must be used. |
 |
UL Listed for Access Control Systems; UL294. |
 |
UL Listed for Fire Alarm Systems; UL1481. |
 |
UL Listed for Burglar Alarm Systems; UL603. |
| |
|
| Specifications - Distribution Board |
 |
Outputs
– 6 Fail Safe or Fail Secure
– Each PTC protected output rated 2.5A @ 23C with a maximum of 2.0A @ 49C.
– Automatic Yellow LED status indication of activated PTC.
– Test push button lights Yellow LED’s to verify their operation.
– Red LED for power on indication. |
 |
Fire Alarm Control Panel Input
– Polarity reversing input.
– Normally open (NO) or normally closed (NC) supervised input with 2.2K Ohm (EOL) resistor.
– Engineering Reset (Optional) normally open (NO) or normally closed (NC) input with 2.2 K Ohm (EOL) resistor. |
 |
Alarm Outputs
– Alarm outputs are Fail Safe
– When FACP activation occurs dry contacts activated.
– Green LED indication when FACP is activated.
– Dry contacts output for power failure to the HPMOM6. |
 |
Board Dimensions: 5.3" L x 3.5" W x 1.0" H (13.46 cm L x 8.89 cm W x 2.54 cm H). |