| Home > Products > Fire Alarm Power Supplies and Communicators |
Fire Alarm Power Supplies and Communicators |
 |
IPGSM-DP
The IPGSM-DP Commercial Fire Communicator is used to upgrade a commercial fire system that previously reported to the Central Station by phone lines (POTS), to a system that uses an Internet or GSM cellular reporting path. The IPGSM-DP communicates via the AlarmNet relay point and has Dual Primary methods of operation. In method one, the unit communicates over the internet as primary and utilizes GSM cellular as a backup, should the internet be unavailable. In method two, the unit communicates via GSM cellular, so no communications cabling is needed. The communications method (IP/GSM or GSM only) is field selectable and easily set up. The unit answers any phone number dialed so Fire Panel programming changes are at a minimum when converting existing systems over to this communications method.
|
|
| Specifications |
 |
Transformer: N8167
Primary – 120VAC, 60Hz
Secondary – 18VAC, 50VA |
 |
Battery back-up: 12V, 7Ah sealed lead acid type (not supplied)
Use a Honeywell 712BNP, Yuasa NP7-12 or equivalent |
 |
Battery Charging Current: maximum 1A |
 |
Transmission power: 850 MHz - 1 Watt, 1900 MHz - 2 Watts |
 |
Dimensions: Width = 12 3/4 inches,
Height = 14 7/8 inches,
Depth = 3 inches |
 |
Supervision: The AC power, backup battery, IP communications, and GSM
communications are monitored. |
|
|