Home  >  Products   >  Power Distribution Modules

Power Distribution Modules


HPACM4

The HPACM4 distributes one (1) 12 to 24 volt AC or DC input over four (4) independently controlled fuse protected outputs. The outputs can also be configured as dry Form "C" contacts. Outputs are activated by an open collector sink or normally open (NO) dry trigger input from an Access Control System, Card Reader, Keypad, Push Button, PIR, etc. This convenient power distribution board has a wide range of applications for access control and security systems including Mag Locks, Electric Strikes, Magnetic Door Holders, etc. Outputs will operate in both fail-safe and fail-secure modes.

The HPACM4 is designed to be powered by one (1) common source which will provide power for both board operation as well as accessory devices, or can be powered by two independent power sources, one (1) for board power and the other for accessory power. The FACP interface can be used for emergency exit, alarm monitoring, HVAC shutdown, elevator recall, or maybe used to trigger other auxiliary devices.

Data Sheet - (36 KB PDF)
Installation Instructions - (239 KB PDF)
Drawing - (545 KB DWG)
 

 

View Listing

Specifications
UL Recognized Component - U.S. and Canada for Access Control Systems (UL294).
12 to 24 volt AC or DC operation (0.6A @ 12 volt, 0.3A @ 24 volt current consumption with all relays energized).
Power Supply Input Options:
   A) One (1) common power input (board and lock power).
   B) Two (2) isolated power inputs (one [1] for board power and one [1] for lock
   power).
Eight (8) Access Control System trigger inputs. Input allows any combination of normally open (NO) inputs or open collector sink inputs.
Eight (8) independently controlled outputs.
Output Options:
   A) Eight (8) fail-safe and/or fail-secure power outputs.
   B) Eight (8) dry Form "C" 5A rated relay outputs.
   C) Any combination of the above.
Eight (8) auxiliary power outputs (unswitched).
Output fuses are rated 3.5A. Main fuse is rated at 10A. Note: Output current is determined by the power supply, not to exceed 10A total.
Red LEDs indicate outputs are triggered (relays energized).
Fire Alarm disconnect (latching or non-latching).
Fire Alarm Disconnect Input Options:
   A) Normally open (NO) or normally closed (NC) dry contact input.
   B) Polarity reversal from FACP signal circuit.
Fire Alarm Disconnect Output Options:
   A) Eight (8) outputs affected.
   B) Four (4) outputs affected, four (4) outputs unaffected (50/50 mode).
FACP output relay (Form "C" contact rated @ 1A, 28VDC not evaluated by UL).
Green LED indicated when FACP disconnect is triggered.
Removable terminal blocks facilitate ease of installation.
Board Dimensions: 8"L x 4.5"W x 1.25"H (cm: 20.32L x 11.43W x 3.175H).
UL Listed: UL294


 

 

Search

 

 

The Honeywell Corporation
HPACM8
HPD8

HPD8CB

 

Where to Purchase Our Products

Find a local sales office or convenient distributor near you.